Balancing choke impedance with VFD rated current capacity requires selecting the right impedance percentage while ensuring the choke can handle the full-load current without saturation. Here's the systematic approach:
Key Selection Criteria
1. Current Rating Must Match or Exceed VFD Rating
Critical: Impedance is specified at rated current — if you exceed this, the choke saturates and impedance drops to near zero.
2. Choose Impedance Based on Application
Rule of thumb:
3. Calculate Choke Impedance
The formula for impedance calculation:
Example for 75 kW (100 HP) VFD:
VFD specs: 400 V, 100 A
Input choke: 3% impedance
Impedance calculation:
Example for 50 kW motor with 80 m cable:
4. Voltage Drop Trade-off
Higher impedance = better filtering but higher voltage drop:
Key insight: The majority of THDi reduction occurs up to 5% for DC choke or 3% for AC line reactor. Above these values, THDi reduction is very low but voltage drop continues to increase.
5. Consider DC Bus Voltage Impact
The additional impedance creates voltage drop on the DC bus, reducing maximum voltage available to motor:
Example: 480 V AC input → 678 V DC (nominal)
With 4.3% DC choke: 16 Ω drop = 29 V loss → ~649 V DC
This matters for high-torque applications near motor speed limits.
Selection Decision Matrix
Practical Example: 75 kW VFD System
System specs:
VFD rated: 75 kW, 400 V, 100 A
Cable length: 80 m
Motor: 50 kW, 75 A
Choke selection:
Result:
Voltage drop: 3% × 400 V = 12 V per choke
Key Takeaway
Optimal balance: Use 3% impedance for both input and output chokes in most VFD applications. This provides:
Good THDi reduction (down to ~43%)
Acceptable voltage drop (12 V at 400 V system)
Always select choke current rating ≥ VFD full-load current + 20% margin to prevent saturation at peak currents.
0 Comments